Cabinet, base-station, data-room and battery-storage cooling — sized to the real heat load, integrated with the enclosure and supported in Australia.

Electronics in outdoor cabinets, shelters, data rooms and battery containers fail from heat and moisture long before anything else. The unit on the wall only fixes that if it matches the heat load, the site and the power available. Prestige Industrial works the problem from that end — then sources the right unit factory-direct and stands behind it locally.
Internal dissipation plus heat gained through the enclosure walls and from the sun — the capacity the site actually needs.
Air conditioner, heat exchanger, combined AC + heat pipe, free cooling or liquid cooling — matched to ambient and energy target.
Single- or three-phase AC, or native DC 48 V telecom power. RS485 on every category, RS485/CAN on liquid-cooling units.
Mounting face, cut-out, sealing and condensate handling on the cabinet, shelter wall, container side or roof.
Operating ranges down to −40 °C, IP55 units, and heating and dehumidification options for cold and humid sites.
Documentation, spares and after-sales in Australia — one accountable team from enquiry to end of life.
Heat-load calculation · model selection with datasheet · dimensions and cut-out information · options schedule (heating, dehumidification, inverter, monitoring) · quotation · commissioning guidance · spares list
Product categories across cabinet, base-station, data-room and battery-storage cooling
Largest unit — in-row data-room cooling, DX or chilled water
Lowest operating temperature across most of the range
Native telecom-power models — no inverter needed on site
Outdoor cabinet coolingSix families cover the enclosures, shelters, rooms and containers that carry electronics. Each family has a full selection table in the series pages.

AC-type (rotary compressor) and DC-type (DC-inverter) units for telecom and industrial outdoor cabinets.

Compressor cooling plus a siphon heat pipe that switches automatically for energy-saving operation.

Air-to-air aluminium plate core with DC centrifugal fans — no compressor, maintenance-free.

A DC 48 V split unit for base stations, and a three-phase unit pairing compressor cooling with fresh-air free cooling.

Precision units between the racks — direct expansion (DX) or chilled water (CW), EC fans, LCD touch screen.

Embedded, side- or top-mounted container air conditioners, plus liquid-cooling units for liquid-cooled battery racks.
RS485 port for remote monitoring on every category; RS485/CAN on liquid-cooling units.
IP55 across the air-conditioner, heat-exchanger and container ranges.
R134a on cabinet and liquid-cooling units; R410a on larger shelter, container and data-room units.
DC-inverter compressors on DC units and on AF / LF models; EC fans on data-room units.
Telecom, industrial automation, power grid, data rooms and energy storage — four duty profiles, each with its own answer on power, mounting and energy use.
Telecom base stationsDC 48 V is already on site, so DC-type cabinet units, heat exchangers and the DC split unit run without an inverter. Free cooling cuts compressor hours where the air is cool and clean.
Industrial & power-grid cabinetsControl, protection and communication cabinets outdoors on AC supply — AC-type cabinet air conditioners with heating for cold mornings, or heat exchangers where ambient allows.
Battery energy storageContainer air conditioners in embedded, side or top mounting for air-cooled racks, and liquid-cooling units with RS485/CAN for liquid-cooled racks.
Data roomsIn-row units between the racks: DX where the room needs its own refrigerant plant, chilled water where a 7–18 °C water supply is available.
The same questions decide every job: how much heat, how hot the site gets, what power is available, and which face of the enclosure the unit can mount on.
| Category | Models | Capacity | Power | Operating range | Page |
|---|---|---|---|---|---|
| Cabinet cooling | |||||
| Cabinet AC — AC type | A06HA1E – A50HA1E | 600 W – 5 kW | 1~220 VAC | −40 … +55 °C | 06 |
| Cabinet AC — DC type | A03NA0E – A40NA0E | 300 W – 4 kW | DC 48 V | −40 … +55 °C | 06 |
| AC + heat exchanger combined | AE15 – AE30 (HA4E / HA0E) | 1.5 – 3 kW + 60 – 120 W/K | DC 48 V (+ 230 VAC) | −40 … +55 °C | 07 |
| Cabinet heat exchanger — DC | H02NA0E – H26NA0E | 25 – 260 W/K | DC 48 V | −40 … +60 °C | 07 |
| Base-station cooling | |||||
| Split AC — DC | A40NA0F | 4 kW | DC 48 V | −40 … +55 °C | 08 |
| AC + free cooling | WAF125NA5S · WAF150NA5S | 12.5 – 15 kW | 3~380 V | −40 … +45 °C | 08 |
| Data-room cooling | |||||
| In-row AC — DX type | CDA12HA5E – CDA45HA5E | 12.5 – 45 kW | 3~380 V | −30 … +45 °C | 09 |
| In-row AC — CW type | CWA12HA5E – CWA45HA5E | 12.5 – 45 kW | 1~230 / 3~380 V | 7 – 18 °C water | 09 |
| Battery-storage cooling | |||||
| Container AC — embedded | A30HC1E – A/AF200HC5E | 3 – 20 kW | 1~230 / 3~380 V | −40 … +45 °C | 10 |
| Container AC — side mounting | A75HC1S – A/AF200HC5S | 7.5 – 20 kW | 1~230 / 3~380 V | −40 … +45 °C | 10 |
| Container AC — top mounting | AF30HC1T – AF200HC5T | 3 – 5 · 12.5 – 20 kW | 1~230 / 3~380 V | −40 … +45 °C | 11 |
| Liquid cooling units | LF30HA1T – LF80HA1B | 3 – 8 kW | 1~230 V | −30 … +55 °C | 11 |
| If the site… | Start with |
|---|---|
| stays well below the target cabinet temperature all year | Cabinet heat exchanger — DC (no compressor, maintenance-free) |
| is sometimes hotter than the target, on DC 48 V, and energy use matters | AC + heat exchanger combined |
| is hotter than the target and has AC mains | Cabinet AC — AC type (heating capacity per model) |
| is hotter than the target and has DC 48 V only | Cabinet AC — DC type |
| is a base-station shelter on DC 48 V power | BTS split AC — DC |
| is a shelter with cool, clean outside air much of the year | BTS AC + free cooling |
| is a data room — own refrigerant plant, or chilled water available | In-row DX · In-row CW |
| is a battery container with air-cooled racks | Container AC — embedded, side or top by mounting face |
| is a battery container with liquid-cooled racks | Liquid cooling units |

For telecom and industrial outdoor cabinets on AC power. Heating and dehumidification options.

For telecom and industrial outdoor cabinets on DC power. Heating optional.
| Model | Cooling | Heating | W×H×D mm |
|---|---|---|---|
| A06HA1E | 600 W | 500 W | 315×546×175 |
| A10HA1E | 1000 W | 1000 W | 446×746×200 |
| A15HA1E | 1500 W | 1000 W | 446×746×200 |
| A20HA1E | 2000 W | 1000 W | 446×746×200 |
| A30HA1E | 3000 W | 1500 W | 485×1150×250 |
| A40HA1E | 4000 W | 1500 W | 485×1150×250 |
| A50HA1E | 5000 W | 3000 W | 600×1300×320 |
| Model | Cooling | Heating | W×H×D mm |
|---|---|---|---|
| A03NA0E | 300 W | Optional | 315×320×140 |
| A06NA0E | 600 W | Optional | 315×546×175 |
| A10NA0E | 1000 W | Optional | 446×746×200 |
| A15NA0E | 1500 W | Optional | 446×746×200 |
| A20NA0E | 2000 W | Optional | 446×746×200 |
| A30NA0E | 3000 W | Optional | 485×1150×250 |
| A40NA0E | 4000 W | Optional | 485×1150×250 |

Dual-system cooling for telecom outdoor cabinets: a compressor cooling unit plus a siphon heat-pipe exchanger, switching automatically for energy-saving operation.
| Model | Cooling | Heat exch. | W×H×D mm |
|---|---|---|---|
| AE15HA4E / HA0E | 1500 W | 60 W/K | 446×746×240 |
| AE20HA4E / HA0E | 2000 W | 80 W/K | 446×746×240 |
| AE25HA4E / HA0E | 2500 W | 100 W/K | 446×746×260 |
| AE30HA4E / HA0E | 3000 W | 120 W/K | 485×1150×300 |

For outdoor cabinets on DC power where the ambient stays below the target inside temperature. No compressor, maintenance-free.
| Model | Heat exchange | W×H×D mm |
|---|---|---|
| H02NA0E | 25 W/K | 270×420×165 |
| H08NA0E | 80 W/K | 400×900×145 |
| H10NA0E | 100 W/K | 412×990×192 |
| H12NA0E | 120 W/K | 412×990×192 |
| H15NA0E | 150 W/K | 518×1246×240 |
| H18NA0E | 180 W/K | 518×1246×240 |
| H26NA0E | 260 W/K | 620×1300×240 |

For telecom base stations and outdoor shelters on DC 48 V power. Split design with a DC-inverter compressor.
| Model | Cooling | Heating | Indoor mm | Outdoor mm |
|---|---|---|---|---|
| A40NA0F | 4000 W | N/A | 950×340×215 | 730×524×292 |

Active compressor cooling plus fresh-air free cooling, switching automatically for energy-saving operation.
| Model | Cooling | Air flow |
|---|---|---|
| WAF125NA5S | 12.5 kW | 3500 m³/h |
| WAF150NA5S | 15.0 kW | 3800 m³/h |
In-row between racks
LCD touch-screen control
DX outdoor condenser| Model | Total cooling | Sensible | EER | Air flow m³/h | Humidification | Indoor W×D×H mm |
|---|---|---|---|---|---|---|
| CDA12HA5E | 12.5 kW | 11.5 kW | 3.5 | 3000 | 3 kg/h | 300×1200×2000 |
| CDA25HA5E | 25 kW | 22.0 kW | 3.3 | 5000 | 3 kg/h | 600×1200×2000 |
| CDA35HA5E | 35 kW | 32.0 kW | 3.4 | 7000 | 3 kg/h | 600×1200×2000 |
| CDA45HA5E | 45 kW | 40.5 kW | 3.3 | 9500 | 6 kg/h | 600×1200×2000 |
| Model | Total cooling | Sensible | EER | Air flow m³/h | Humidification | Power | Indoor W×D×H mm |
|---|---|---|---|---|---|---|---|
| CWA12HA5E | 12.5 kW | 11.8 kW | 3.5 | 2800 | 3 kg/h | 1~230 V | 300×1200×2000 |
| CWA25HA5E | 25 kW | 23.0 kW | 3.3 | 4800 | 3 kg/h | 1~230 V | 600×1200×2000 |
| CWA35HA5E | 35 kW | 33.0 kW | 3.4 | 7000 | 3 kg/h | 3~380 V | 600×1200×2000 |
| CWA45HA5E | 45 kW | 41.0 kW | 3.3 | 9000 | 6 kg/h | 3~380 V | 600×1200×2000 |
Catalogue energy-efficiency ratio across both DX and CW sizes.
Optional humidifier sized per model — 6 kg/h on the 45 kW units.
CW units run on 7 – 18 °C supply — high water temperature, lower chiller energy.


| Model | Cooling | Heating | Power | Rated condition | W×H×D mm |
|---|---|---|---|---|---|
| A30HC1E | 3.0 kW | 2.0 kW | 1~230 V | L35 / L35 °C | 500×1300×250 |
| A50HC1E | 5.0 kW | 3.0 kW | 1~230 V | L35 / L35 °C | 600×1300×320 |
| A75HC1E | 7.5 kW | 3.0 kW | 1~230 V | L35 / L35 °C | 660×1600×400 |
| A100HC1E | 10.0 kW | 6.0 kW | 1~230 V | L35 / L35 °C | 660×1600×400 |
| A125HC5E / AF125HC5E | 12.5 kW | 6.0 kW | 3~380 V | L27 / L35 °C | 800×2100×600 |
| A150HC5E / AF150HC5E | 15.0 kW | 9.0 kW | 3~380 V | L27 / L35 °C | 800×2100×600 |
| A200HC5E / AF200HC5E | 20.0 kW | 9.0 kW | 3~380 V | L27 / L35 °C | 800×2100×600 |
| Model | Cooling | Heating | Power | Rated condition | W×H×D mm |
|---|---|---|---|---|---|
| A75HC1S | 7.5 kW | 3.0 kW | 1~230 V | L35 / L35 °C | 660×1600×400 |
| A10HC1S | 10.0 kW | 6.0 kW | 1~230 V | L35 / L35 °C | 660×1600×400 |
| A120HC1E | 12.0 kW | 6.0 kW | 1~230 V | L35 / L35 °C | 660×1600×400 |
| A125HC5S / AF125HC5S | 12.5 kW | 6.0 kW | 3~380 V | L27 / L35 °C | 800×2100×705 |
| A150HC5S | 15.0 kW | 9.0 kW | 3~380 V | L27 / L35 °C | 800×2100×705 |
| AF150HC5S | 15.0 kW | 6.0 kW | 3~380 V | L27 / L35 °C | 800×2100×703 |
| A200HC5S / AF200HC5S | 20.0 kW | 9.0 kW | 3~380 V | L27 / L35 °C | 800×2100×705 |


Roof-mounted units for industrial and battery energy-storage shelters: high-efficiency DC-inverter rotary compressor, RS485, heating, dehumidification and an ambient intake filter built in. IP55 · −40 to +45 °C · R410a.
| Model | Cooling | Heating | Air flow | Power | Rated condition | W×D×H mm |
|---|---|---|---|---|---|---|
| AF30HC1T | 3.0 kW | 1.5 kW | 1000 m³/h | 1~230 V | L25 / L35 °C | 870×1000×350 |
| AF40HC1T | 4.0 kW | 2.0 kW | 2000 m³/h | 1~230 V | L25 / L35 °C | 870×1000×350 |
| AF50HC1T | 5.0 kW | 2.0 kW | 2000 m³/h | 1~230 V | L25 / L35 °C | 870×1000×350 |
| AF125HC5T | 12.5 kW | 6.0 kW | 3600 m³/h | 3~380 V | L27 / L35 °C | 1200×1780×603 |
| AF150HC5T | 15.0 kW | 9.0 kW | 5000 m³/h | 3~380 V | L27 / L35 °C | 1200×1780×603 |
| AF200HC5T | 20.0 kW | 9.0 kW | 5500 m³/h | 3~380 V | L27 / L35 °C | 1200×1780×603 |

For battery energy-storage shelters with liquid-cooled racks.
| Model | Cooling | Heating | Water flow | Mounting | Dehumidification | W×H×D mm |
|---|---|---|---|---|---|---|
| LF30HA1T | 3.0 kW | 1.0 kW | 25 L/min | Top | Optional | 702×280×932 |
| LF50HA1T | 5.0 kW | 2.0 kW | 45 L/min | Top | Optional | 702×280×932 |
| LF30HA1B | 3.0 kW | 1.0 kW | 25 L/min | Vertical | N/A | 275×800×1100 |
| LF50HA1B | 5.0 kW | 2.0 kW | 45 L/min | Vertical | N/A | 275×800×1100 |
| LF80HA1B | 8.0 kW | 2.0 kW | 50 L/min | Vertical | N/A | 275×1040×1150 |
High-efficiency rotary on AC-type units; DC-inverter on DC-type and AF / LF models.
Environment-friendly refrigerant on the cabinet range; R410a on larger shelter and container units.
Heating capacity listed per model on AC-type units, optional on DC-type; dehumidification optional.

Temperature, status and alarms into the site monitoring system.
High protection level for outdoor cabinets exposed to dust and weather.
Rated for −40 to +55 °C ambient — for both high- and low-temperature regions.
| Category | Power | Monitoring | Mounting | Refrigerant |
|---|---|---|---|---|
| Cabinet AC — AC type | 1~220 VAC ±15%, 50 Hz | RS485 | Outdoor cabinet | R134a |
| Cabinet AC — DC type | DC 48 V ±20% | RS485 | Outdoor cabinet | R134a |
| AC + heat exchanger | DC 48 V (+ 1~230 VAC on HA4E) | RS485 | Outdoor cabinet | R134a |
| Heat exchanger — DC | DC 48 V ±20% | RS485 | Outdoor cabinet | — (no refrigerant) |
| BTS split — DC | DC 48 V ±20% | RS485 | Wall-mounted, split | R134a |
| BTS AC + free cooling | 3~380 V ±15%, 50 Hz | RS485 | Wall-mounted | R410a |
| In-row DX / CW | 3~380 V (CW12/25: 1~230 V) | RS485 · LCD | In the rack row | R410a (DX) |
| Container AC | 1~230 V or 3~380 V | RS485 | Embedded · side · top | R410a (A30HC1E: R134a) |
| Liquid cooling | 1~230 V ±15%, 50/60 Hz | RS485 / CAN | Top · vertical | R134a |
Rule of thumb for a sealed enclosure:
A = exposed surface area (m²); k ≈ 5.5 W/m²·K for painted sheet steel. Add a margin for direct sun, then take the next size up.
Heat exchangers only work while outside air is cooler than the target inside:
q is the specific capacity in W/K — compare it with the H-series table on page 07. If the gap is small or negative, use an air conditioner.
Compressor units remove moisture from the cabinet air — plan the drain route on the mounting face.
A closed loop only stays closed if the cut-out and cable entries are sealed — see our cable entry range.
Keep the external air path free of walls and neighbouring units so the condenser can reject heat.




One team from the first heat-load question to the last spare part — specified in Australia, sourced factory-direct.
Equipment, enclosure, location, power available and monitoring system.
Internal dissipation, wall and solar gain, worst-case ambient.
Heat exchanger, AC, hybrid, free cooling or liquid — by ambient and energy target.
Capacity with margin, power, mounting, heating, dehumidification, monitoring.
Selection, datasheet, dimensions and cut-out information with the price.
Factory-direct sourcing, inspection and delivery to site or integrator.
Mounting, sealing, condensate and RS485 / alarm wiring into the enclosure.
Commissioning help, documentation, spares and local after-sales.
Outdoor cabinets
Energy storage
Data rooms
Tell us what is in the enclosure, where it stands and what power is available. We will select the technology and capacity, confirm the options and quote it — factory-direct, supported in Australia.